  1. pin-int

Honeywell W973J1017 Logic Panel, 24 VAC, 4-1/8 in W x 6-1/4 in H x 2-5/16 in D

Honeywell W973J1017 Logic Panel, 24 VAC, 4-1/8 in W x 6-1/4 in H x 2-5/16 in D

  • Manufacturer: Honeywell International Inc
  • Brand Name: Honeywell
  • Part#: HNWW973J1017
  • MPN: W973J1017
  • Min. Order Qty: 1
  • Qty. Interval: 1
  • Availability: loading
  • Branch Availability

Honeywell Logic Panel, 24 VAC, 8 VA VA Rating, 50/60 Hz, 1/4 in Quick Connect Male Terminal, 4 Heat/4 Cool Stages, Staged On/Off Outputs, 40 to 150 deg F, 4-1/8 in W x 6-1/4 in H x 2-5/16 in D

Dimensions      :      4-1/8 in W x 6-1/4 in H x 2-5/16 in D
Electrical Connection      :      1/4 in Quick Connect Male Terminal
Frequency Rating      :      50/60 Hz
Outputs      :      Staged On/Off
Stages      :      4 Heat/4 Cool
Temperature Rating      :      40 to 150 deg F
VA Rating      :      8 VA
Voltage Rating      :      24 VAC
  • Proven, reliable temperature control
  • Many flexible versions to meet your application needs
  • Panels can be used with staged gas, oil or electric heat, modulating gas, hot water or steam heat and direct expansion or modulating chilled water cooling
  • Control upto 3 on-off heat or cool stages or upto 10 on-off heat and/or cool stages using W975 satellite sequencers
  • Modulating DC current signal controls economizer heating or cooling valve motors
  • T7067 dual set point thermostat/transmitter located in controlled space provides heating and cooling input signal based on space demand
  • C7046A sensor located in discharge air duct provides heating/cooling anticipation and economizer modulating low limit signal
  • System cycles all stages off on power interruption
  • When power is restored, system sequences required stages on with timed inter-stage delay
  • pdfCatalog https://assets.unilogcorp.com/267/ITEM/DOC/Honeywell_S963B1136_Catalog.pdf
  • pdfInstruction/Installation Manual https://assets.unilogcorp.com/267/ITEM/DOC/Honeywell_W973J1017_Instruction_Installation_Manual.pdf
  • pdfCatalog https://assets.unilogcorp.com/267/ITEM/DOC/Honeywell_S963B1136_Catalog.pdf
  • pdfInstruction/Installation Manual https://assets.unilogcorp.com/267/ITEM/DOC/Honeywell_W973J1017_Instruction_Installation_Manual.pdf